Email:[email protected]

This European Standard describes the method to evaluate the performance of protective systems for electrical cable and busbar systems in order to maintain the circuit integrity under fire conditions to classify the protective system according to EN 13501 3 for the P classification. The test examines the behaviour of cable protection systems exposed to fire from outside. The tests specified in this standard are not aimed for assessing the performance of the fire protective system and the penetration seal for maintaining the requirements of the penetrated wall or ceiling (classification E / I). This method is very different to EN 50200 for the PH classification and also to IEC 60331 11, IEC 60331 21, IEC 60331 23, and IEC 60331 25, which are not designed for fire protective systems for electrical cable systems. This standard should be used in conjunction with EN 1363 1. The test results apply to fire protective systems for electrical cable systems rated for voltages up to 1 kV. The test procedure should also be used to determine the performance of protective systems for use with data and optical cables, however, verification procedures for such cables are still under development. Proposals are given in Annex C. The protective system may include ventilation devices, inspection hatches, fixed or removable lids etc. The tests specified in this standard are not aimed for assessing the performance of sprayed or painted coatings (e.g. intumescent or ablative coating, plastic film, epoxy resin) and similar protective layers (e.g. wrap, bandage) applied directly on the cables or bus bars as fire protective system. Also, cables and bus bars with intrinsic resistance to fire, and without fire protective systems around, are excluded (see CENELEC standard EN 50577). This test method is not applicable for cabinets for electrical accessory containing bus systems, relays or similar. Dieses Prüfverfahren gilt nicht für Schaltschränke für elektrische Zubehörteile wie Bussysteme, Relais u. ä.

PDF Catalog

PDF Pages PDF Title
2 undefined
8 1 Scope
2 Normative references
9 3 Terms and definitions
11 4 Test equipment
4.1 Furnace
5 Test conditions
5.1 Heating conditions
5.2 Pressure conditions
6 Test specimen
6.1 Dimensions
6.2 Number of tests
6.3 Design
12 7 Installation of test specimen
7.1 Fire protective system with cables
14 7.2 Fire protective systems with busbars
7.3 Special cases
15 8 Conditioning
9 Application of instrumentation
9.1 Furnace thermocouples (plate thermocouples)
9.2 Preheating inside the fire protective system
9.3 Additional thermocouples
16 10 Test procedure
10.1 General
10.2 Power supply
18 11 Performance criteria
12 Test report
19 13 Field of direct application of test results
13.1 Types of cables
13.2 Application of test results of four-sided, three sided or two-sided fire protective systems
21 13.3 Assembly of fire protective system
22 13.4 Fixing of fire protective system to wall and ceiling
23 13.5 Types of cable management systems / busbars and load inside the fire protective system
13.6 Types of suspension device
24 13.7 Adjoining construction
25 13.8 Dimension of fire protective systems
13.9 Orientation of fire protective systems for cables and busbars
13.10 Special cases
33 Annex A (informative)Thermocouples inside the fire protective systems
34 Annex B (informative)Preheating
35 Annex C (informative)Performance criteria for communication/data cables
BS EN 1366-11:2018+A1:2021