Shopping Cart

No products in the cart.

BS EN 62606:2013+A1:2017:2018 Edition

$215.11

General requirements for arc fault detection devices

Published By Publication Date Number of Pages
BSI 2018 192
Guaranteed Safe Checkout
Categories: ,

If you have any questions, feel free to reach out to our online customer service team by clicking on the bottom right corner. Weโ€™re here to assist you 24/7.
Email:[email protected]

This International Standard applies to arc fault detection devices (AFDDs) for household and similar uses, intended to be used in a.c. circuits, for rated voltages not exceeding 440 V a.c, with rated frequencies of 50 Hz, 60 Hz or 50/60 Hz and rated currents not exceeding 63 A.

NOTE 1 In the USA, Arc Fault Circuit Interrupters (AFCI) are considered similar to AFDDs.

An AFDD is designed by the manufacturer:

  • either as a single device having opening means able to open the protected circuit in specified conditions; or

  • as a single device integrating a protective device; or

  • as a separate unit, according to Annex D assembled on site with a declared protective device.

The integrated protection device is either a circuit-breaker in accordance with IEC 60898-1 or an RCD in accordance with IEC 61008-1, IEC 61009-1 or IEC 62423.

These devices are intended to mitigate the risk of fire in a final circuit of a fixed installation due to the effect of arc fault currents that pose a risk of fire ignition under certain conditions if the arcing persists.

Protection against fire ignition due to overvoltage due to a broken neutral within a three phase installation to be included in this type of equipment as an additional option is under consideration in 9.22.

NOTE 2 Tracking current leads to arcing and therefore may ignite fire.

This International Standard applies to devices performing simultaneously the detection and discrimination of arcing current with regards to fire hazards and defines operating criteria under specified conditions for the opening of the circuit when the arcing current exceeds the limit values given in this standard.

AFDDs complying with this standard, with the exception of those with an uninterrupted neutral, are suitable for use in IT systems.

Text deleted

AFDDs energised from batteries or a circuit other than the protected circuit are not covered by this standard.

AFDDs provide isolation, they are intended to be operated by uninstructed persons and do not require maintenance.

Particular requirements may be necessary for:

  • AFDDs incorporated in or intended only for association with plugs and socket-outlets or with appliance couplers for household or similar general purposes;

  • AFDDs intended to be used at frequencies other than 50 Hz or 60 Hz.

NOTE 3 For AFDDs incorporated in, or intended only for socket-outlets the requirements of this standard can be used, as far as applicable, in conjunction with the requirements of IEC 60884-1 or the national requirements of the country where the product is placed on the market.

NOTE 4 In the UK, the plug part and the socket-outlet part(s) need not comply with any IEC 60884-1 requirements. In the UK, the plug part shall comply with BS 1363-1 and the socket-outlet part(s) shall comply with BS 1363-2.

Special precautions (e.g. surge protective devices) may be necessary when excessive overvoltages are likely to occur on the supply side.

The requirements of this standard apply for standard conditions of temperature and environment. They are applicable to AFDDs intended for use in an environment with pollution degree 2. Additional requirements may be necessary for devices used in locations having more severe environmental conditions.

NOTE 5 AFDD for d.c. applications are under consideration.

PDF Catalog

PDF Pages PDF Title
2 undefined
33 English
CONTENTS
40 INTRODUCTION
41 1 Scope
42 2 Normative references
43 3 Terms and definitions
46 4 Classification
4.1 According to the method of construction
4.2 According to the method of mounting and connection
4.3 According to the number of poles and current paths
4.4 AFDD providing monitoring information
5 Characteristics of AFDDs
5.1 Summary of characteristics and conditions to mitigate the risk of fire
47 5.2 Rated quantities and other characteristics
5.2.1 Rated voltage
5.2.2 Rated current (In)
5.2.3 Rated frequency
5.2.4 Rated making and breaking capacity (Im)
48 5.2.5 Rated making and breaking capacity on one pole (Im1)
5.3 Standard and preferred values
5.3.1 Preferred values of rated voltage (Un)
5.3.2 Preferred values of rated current (In)
5.3.3 Preferred values of rated frequency
5.3.4 Minimum value of the rated making and breaking capacity (Im)
5.3.5 Minimum value of the rated making and breaking capacity on one pole (Im1)
5.3.6 Standard and preferred values of the rated conditional short-circuit current (Inc) and standard and preferred values of the rated conditional short circuit current for one pole (Inc1)
49 5.3.7 Limiting values of operating criteria for AFDDs for low and high arc currents
Tables
Table 1 โ€“ Limit values of break time for Un = 230 V AFDDs
Table 2 โ€“ Limit values of break time for Un = 120 V AFDDs
Table 3 โ€“ Maximum allowed number of arcing half-cycles within 0,5 sfor Un 230 V AFDDs and Un = 120 V AFDDs
50 5.4 Standard value of rated impulse withstand voltage (Uimp)
5.5 Coordination with short-circuit protective devices (SCPDs)
5.5.1 General
5.5.2 Rated conditional short-circuit current (Inc) and rated conditional short-circuit on one pole (Inc1)
5.5.3 Operating characteristics of opening means for AFDDs according to 4.1.1
Table 4 โ€“ Rated impulse withstand voltage as a function of the nominal voltage of the installation
51 6 Marking and other product information
6.1 Marking
Table 5 โ€“ Marking and position of marking
53 6.2 Additional marking for AFDDs according to 4.1.1
6.2.1 Marking of AFDDs
6.2.2 Instructions for wiring and operation
54 7 Standard conditions for operation in service and for installation
7.1 Standard conditions
7.2 Conditions of installation
7.3 Pollution degree
Table 6 โ€“ Standard conditions for operation in service
55 8 Requirements for construction and operation
8.1 General
8.2 Mechanical design
8.2.1 General
56 8.2.2 Mechanism
57 8.2.3 Clearances and creepage distances (see Annex B)
58 Table 7 โ€“ Minimum clearances and creepage distances (1 of 2)
60 8.2.4 Screws, current-carrying parts and connections
8.2.5 Terminals for external conductors
61 Table 8 โ€“ Connectable cross-sections of copper conductors for screw-type terminals
62 8.3 Protection against electric shock
63 8.4 Dielectric properties and isolating capability
8.5 Temperature rise
8.5.1 Temperature-rise limits
64 8.5.2 Ambient air temperature
8.6 Operating characteristics
8.6.1 Operating characteristics of the protective device part
8.6.2 Operating characteristics
Table 9 โ€“ Temperature-rise values
65 8.7 Mechanical and electrical endurance
8.8 Performance at short-circuits currents
8.9 Resistance to mechanical shock and impact
8.10 Resistance to heat
8.11 Resistance to abnormal heat and to fire
8.12 Behaviour of AFDDs in case of overcurrents in the main circuit
66 8.13 Behaviour of AFDDs in case of current surges caused by impulse voltages
8.14 Reliability
8.15 Electromagnetic compatibility (EMC)
8.16 Masking test for correct operation behaviour in presence of various appliances connected to the load side
8.17 Performance of the AFD test device
67 9 Testing procedure
9.1 General
9.1.1 General testing procedure for the different type of AFDDs
9.1.2 The characteristics of AFDDs are checked by means of type tests
68 9.1.3 For certification purposes, type tests are carried out in test sequences.
9.1.4 Routine tests to be carried out by the manufacturer on each device
9.2 Test conditions
Table 10 โ€“ List of type tests
69 9.3 Test of indelibility of marking
Table 11 โ€“ Test copper conductors corresponding to the rated currents
70 9.4 Test of reliability of screws, current-carrying parts and connections
Table 12 โ€“ Screw thread diameters and applied torques
71 9.5 Test of reliability of terminals for external conductors
Table 13 โ€“ Pulling forces
72 9.6 Verification of protection against electric shock
73 9.7 Test of dielectric properties
9.7.1 General
9.7.2 Resistance to humidity
9.7.3 Insulation resistance of the main circuit
74 9.7.4 Dielectric strength of the main circuit
75 9.7.5 Insulation resistance and dielectric strength of auxiliary circuits
9.7.6 Capability of control circuits connected to the main circuit in respect of withstanding high d.c. voltages due to insulation measurements
Table 14 โ€“ Test voltage of auxiliary circuits
76 9.7.7 Verification of impulse withstand voltages (across clearances and across solid insulation) and of leakage current across open contacts
77 Table 15 โ€“ Test voltage for verification of impulse withstand voltage
78 Table 16 โ€“ Test voltage for verifying the suitability for isolation, referred to the rated impulse withstand voltage of the AFDD and the altitude where the test is carried out
79 9.8 Test of temperature-rise
9.8.1 Ambient air temperature
80 9.8.2 Test procedure
9.8.3 Measurement of the temperature of parts
9.8.4 Temperature-rise of a part
9.9 Verification of the operating characteristics
9.9.1 General
9.9.2 Series arc fault tests
83 9.9.3 Parallel arc fault tests
85 9.9.4 Masking test, verification of correct operation
86 9.9.5 Unwanted tripping test
87 9.10 Verification of mechanical and electrical endurance
9.10.1 General test conditions
88 9.10.2 Test procedure
9.10.3 Condition of the AFDD after test
9.11 Verification of the behaviour of the AFDD under short-circuit conditions
9.11.1 General
89 9.11.2 Short-circuit tests for AFDDs according to 4.1.1
90 Table 17 โ€“ Tests to be made to verify the behaviour of AFDDsunder short-circuit conditions
91 Table 18 โ€“ Minimum values of l2t and lp
92 Table 19 โ€“ Power factors for short-circuit tests
97 9.12 Verification of resistance to mechanical shock and impact
9.12.1 Mechanical shock
9.12.2 Mechanical impact
100 9.13 Test of resistance to heat
101 9.14 Test of resistance to abnormal heat and to fire
102 9.15 Verification of the trip-free mechanism
9.15.1 General test conditions
9.15.2 Test procedure
9.16 Test of resistance to rusting
9.17 Verification of limiting values of the non-operating current under overcurrent conditions
103 9.18 Verification of behaviour of AFDDs in case of current surges caused by impulse voltages
9.18.1 General
9.18.2 Verification of behaviour at surge currents up to 3 000 A (8/20 ฮผs surge current test)
9.19 Verification of reliability
9.19.1 General
104 9.19.2 Climatic test
105 9.19.3 Test with temperature of 40 ยฐC
106 9.20 Verification of ageing of electronic components
9.21 Electromagnetic compatibility (EMC)
9.21.1 General
9.21.2 EMC tests covered by other clauses of the present standard
9.21.3 EMC tests to be performed
Table 20 โ€“ Tests already covered in this standard
107 Table 21 โ€“ Tests to be applied for EMC
108 9.21.4 AFDDs Performance criteria
109 9.22 Verification of protection due to overvoltage due to a broken neutral in a three phase system
Figures
Figure 1 โ€“ Thread forming tapping screw
Figure 2 โ€“ Thread cutting tapping screw
110 Figure 3 โ€“ Standard test finger (9.6)
111 Figure 4 โ€“ Test circuit for series arc fault tests
Figure 5 โ€“ Arc generator
Figure 6 โ€“ Test circuit for parallel arc fault tests
Figure 7 โ€“ Test circuit for parallel arc cable cutting test
112 Figure 8 โ€“ Test apparatus
Figure 9 โ€“ Test for verification of correct operation in case of parallel arc to ground
Figure 10 โ€“ Test circuit for masking tests (inhibition and disturbing loads)
113 Figure 11 โ€“ Test configuration for masking tests
Figure 12 โ€“ EMI filter 1 for masking tests
114 Figure 13 โ€“ EMI filter 2 for masking tests
Figure 14 โ€“ EMI filter description installed in Figure 13
Figure 15 โ€“ Test circuit for masking tests with line impedance
115 Figure 16 โ€“ Cross talk test
Figure 17 โ€“ Controlled current test circuit
116 Figure 18 โ€“ Controlled current with delay angle 45 ยฐ, 90 ยฐ and 135 ยฐ
117 Figure 19 โ€“ Short circuit test
118 Figure 20 โ€“ Typical diagram for short circuit tests ((9.11.2.4c)
119 Figure 21 โ€“ Detail of impedance Z, Z1 and Z2
Figure 22 โ€“ Example of calibration record for short-circuit test (9.11.2.2 j)
120 Figure 23 โ€“ Mechanical shock test apparatus (9.12.1)
121 Figure 24 โ€“ Mechanical impact test apparatus (9.12.2.2)
122 Figure 25 โ€“ Striking element for pendulum impact test apparatus (9.12.2.2)
123 Figure 26 โ€“ Mounting support for sample for mechanical impact test (9.12.2.2)
124 Figure 27 โ€“ Example of mounting of unenclosed AFDDfor mechanical impact test (9.12.2.2)
125 Figure 28 โ€“ Example of mounting of panel mounting type AFDDfor the mechanical impact test (9.12.2.2)
126 Figure 29 โ€“ Application of force for mechanical testof rail mounted AFDD (9.12.2.3)
Figure 30 โ€“ Ball-pressure test apparatus (9.13.2)
127 Figure 31 โ€“ Surge current impulse 8/20 (s
Figure 32 โ€“ Test circuit for the surge current test at AFDDs
128 Figure 33 โ€“ Stabilizing period for reliability test (9.19.2.3)
129 Figure 34 โ€“ Reliability test cycle (9.19.2.3)
130 Figure 35 โ€“ Example for test circuit for verification of ageingof electronic components (9.20)
Figure 36 โ€“ Preparation of the cable specimens (9.9.2.6)
Figure 37 โ€“ Example of arc voltage and current waveform obtained with cable specimen
131 Annex A (normative) Test sequence and number of samples to be submitted for certification purposes
132 Table A.1 โ€“ Test sequences for AFDDs classified according to 4.1.1
133 Table A.2 โ€“ Test sequences for AFDDs classified according to 4.1.2
134 Table A.3 โ€“ Test sequences for AFDDs classified according to 4.1.3
135 Table A.4 โ€“ Number of samples for full test procedure
137 Table A.5 โ€“ Number of samples for simplified test procedure
138 Annex B (normative) Determination of clearances and creepage distances
143 Annex C (normative) Arrangement for the detection of the emission ofionized gases during short-circuit tests
144 Figure C.1 โ€“ Test arrangement
145 Figure C.2 โ€“ Grid
Figure C.3 โ€“ Grid circuit
146 Annex D (normative) Additional requirements and tests for AFDDs accordingto the classification 4.1.3 designed to be assembled on site together with a main protective device (circuit-breaker or RCCB or RCBO)
150 Annex E (normative) Routine tests
151 Annex F (informative) Description of the shaker arc test in 9.10.2
Figure F.1 โ€“ Gap Measurement
Figure F.2 โ€“ Shaker arc test table with Loose Terminals
152 Figure F.3 โ€“ AFDD connected to the shaker arc table during test
153 Annex IA (informative) Methods of determination of short-circuit power-factor
155 Annex IB (informative)
Examples of terminal designs
Figure IB.1 โ€“ Examples of pillar terminals
156 Figure IB.2 โ€“ Examples of screw terminals and stud terminals
157 Figure IB.3 โ€“ Examples of saddle terminals
Figure IB.4 โ€“ Examples of lug terminals
158 Annex IC (informative) Correspondence between ISO and AWG copper conductors
159 Annex ID
(informative)
Follow-up testing program for AFDDs
Table ID.1 โ€“ Test sequences during follow-up inspections
162 Table ID.2 โ€“ Number of samples to be tested
163 Annex IE
(informative)
SCPDs for short-circuit tests
Table IE.1 โ€“ Indication of silver wire diameters as a function of rated currents and short-circuit currents
164 Figure IE-1 โ€“ Test apparatus for the verification of the minimum I2t and Ip values to be withstood by the AFDD
165 Annex J (normative) Particular requirements for AFDDs with screwless type terminals for external copper conductors
167 Table J.1 โ€“ Connectable conductors
168 Table J.2 โ€“ Cross-sections of copper conductorsconnectable to screwless-type terminals
169 Table J.3 โ€“ Pull forces
170 Figure J.1 โ€“ Connecting samples
172 Figure J.2 โ€“ Examples of screwless-type terminals
173 Annex K (normative) Particular requirements for AFDDs with flat quick-connect terminations
174 Table K.1 โ€“ Informative table on colour code of female connectors in relationship with the cross section of the conductor
175 Table K.2 โ€“ Overload test forces
176 Figure K.1 โ€“ Example of position of the thermocouple for measurement of the temperature-rise
Table K.3 โ€“ Dimensions of tabs
177 Figure K.2 โ€“ Dimensions of male tabs
178 Figure K.3 โ€“ Dimensions of round dimple detents (see Figure K.2)
Figure K.4 โ€“ Dimensions of rectangular dimple detents (see Figure K.2)
Figure K.5 โ€“ Dimensions of hole detents
179 Figure K.6 โ€“ Dimensions of female connectors
Table K.4 โ€“ Dimensions of female connectors
180 Annex L (normative) Specific requirements for AFDDs with screw-type terminals for external untreated aluminium conductors and with aluminium screw-type terminals for use with copper or with aluminium conductors
181 Table L.1 โ€“ Marking for terminals
182 Table L.2 โ€“ Connectable cross-sections of aluminium conductors for screw-type terminals
183 Table L.3 โ€“ List of tests according to the material of conductors and terminals
Table L.4 โ€“ Connectable conductors and their theoretical diameters
184 Table L.5 โ€“ Cross sections (S) of aluminium test conductors corresponding to the rated currents
185 Table L.6 โ€“ Test conductor length
Table L.7 โ€“ Equalizer and busbar dimensions
187 Table L.8 โ€“ Test current as a function of rated current
Table L.9 โ€“ Example of calculation for determining the average temperature deviation D
188 Figure L.1 โ€“ General arrangement for the test
Figure L.2 โ€“ Example for the use of the terminals in the AFDD
189 Figure L.3 โ€“ Example for the use of the terminals in the AFDD
Figure L.4 โ€“ Example for the use of the terminals in the AFDD
Figure L.5 โ€“ Example for the use of the terminals in the AFDD
Figure L.6 โ€“ Example for the use of the terminals in the AFDD
190 Bibliography
BS EN 62606:2013+A1:2017
$215.11